Troubleshooting
Installation Handbook, AutroFlame X33AF PL Multispectrum IR Flame Detector, 116-P-X33AF/PL/DE, 2005-12-12,
Autronica Fire and Security AS
Page 16
6. Troubleshooting
WARNING: The “front’ half of the detector contains no user
serviceable components and should never be opened. The terminal
compartment is the only part of the enclosure that should be opened
by the user in the field.
Disable any extinguishing equipment that is connected to the unit.
Inspect the viewing windows for contamination and clean as
necessary. The detector is relatively insensitive to airborne
contaminants; however, thick deposits of ice, dirt, or oil will reduce
sensitivity. (Refer to the “Maintenance” section for complete
information regarding cleaning of the detector viewing
windows.)
Check input power to the unit (18 – 30V DC on terminals 1, 3 and 15,
18. Ref. fig. 4)
Check the fire panel display for fault status.
If all wiring checks out (no wire fault warnings on the panel display)
and cleaning of the oi plate/window did not correct the fault condition,
check for high levels of background IR radiation by covering the
detector with the factory supplied cover or aluminum foil. If the fault
condition on the detector LED clears within 6 minutes or less, extreme
background IR is present. Re-adjust the view of the detector away
from the IR source or relocate the detector.
If none of these actions corrects the problem, return the detector to
the factory for repair.
NOTE: It is highly recommended that a complete spare be kept on
hand for field replacement to ensure continuous protection.
6.1 Periodic Checkout Procedure
A checkout of the system using the magnetic oi feature should be
performed on a regularly scheduled basis to ensure that the system is
operating properly. To test the system, perform the “Fire Alarm Test”
described above.
NOTE: Autromatic alarm-path testing is provided by the system once
every 24 hours (This test does not activate any outputs or alarm
indications on the panel).