Autronica AutroFlame X33AF Spécifications Page 11

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 38
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 10
General Application Information
Installation Handbook, AutroFlame X33AF PL Multispectrum IR Flame Detector, 116-P-X33AF/PL/DE, 2005-12-12,
Autronica Fire and Security AS
Page 9
3.2.3 EMI/RFI Interference
The X33AF PL is resistant to interference by EMI and RFI, and is
EMC Directive compliant. It will not respond to a 5-watt walkie-talkie at
distances greater than 1 foot (0.3m). Do not operate a walkie-talkie
within 1 foot (0.3m) of the X33AF PL.
3.2.3.1 Non-Carbon Fires
The X33AF PL is a multiple spectrum IR device with detection limited
to carbonaceous fuels. It should not be used to detect fires from fuels
that do not contain carbon, such as hydrogen, sulphur and burning
metals.
Vue de la page 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 37 38

Commentaires sur ces manuels

Pas de commentaire