Installation
Installation Handbook, AutroFlame X33AF PL Multispectrum IR Flame Detector, 116-P-X33AF/PL/DE, 2005-12-12,
Autronica Fire and Security AS
Page 13
5.2 Protection Against Moisture Damage
It is important to take proper precautions during installation to ensure
that moisture will not come in contact with the electrical connections or
components of the system. The integrity of the system regarding
moisture protection must be maintained for proper operation and is
the responsibility of the installer.
If conduit is used, drains must be installed at water collection points to
automatically drain accumulated moisture. Conduit breathers should
be installed at upper locations to provide ventilation and allow water
vapour to escape. At least one breather should be used with each
drain.
Conduit raceways should be inclined so that water will flow to low
points for drainage and will not collect inside enclosures or on conduit
seals. If this is not possible, install conduit drains above the seals to
prevent the collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the loop.
Conduit seals may be required for compliance with explosion-proof
installation requirements. Units with M25 thread must use an IP66
washer to prevent water ingress.
5.3 Wiring Procedure
5.3.1 Wire Size and Type
The X33AF PL can only be used with the AutroSafe IFG system, and
must be connected to the BSD-340 PowerLoop driver.
The system should be wired using a "14 to 24 gauge" (2.0 - 0.2 mm
2
)
cable. The wire size selected should be based on the number of
detectors connected, and the cable length. The PowerLoop calculator
of the AutroSafe IFG configuration tool must be used to determine the
cable dimension.
NOTE: Refer to the “Power Consumption” in the “Specifications”
section of this manual.
The use of shielded cable is required to protect against interference
caused by EMI and RFI. When using cables with shields, terminate
the shields as shown in figure 4. Consult the factory if not using
shielded cable.
In applications where the wiring cable is installed in conduit, the
conduit should not be used for wiring to other electrical equipment.
CAUTION: qualified personnel should perform Installation of the
detector and wiring only.