Changes on the Panel Bus
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 68
15. Changes on the Panel Bus
15.1 Typical Scenarios
This chapter provides information on how changes are to be carried
out on the panel bus (typical scenarios), plus the panel indication
(visual/audible) and the results of the changes.
15.2 Adding an extra panel to the Panel Bus
Step Task Expected results
For example, an Information Panel BV-210 is added to the Panel Bus.
1
The system is to be in quiescent
condition.
Enter access level 3 (service
mode).
2
Add a new panel to the panel bus.
Make sure that the panel’s
address (refer to Addressing
Panels, chapter 6) is not already
used for other existing panels.
Within 100 seconds the Fault indicator starts to pulse and the
internal buzzer is turned on.
The panel display shows the following message:
“Panel topology mismatch”
3
Press the Mute Panel button The internal buzzer is turned off.
4
Acknowledge the fault by pressing
the Function button, then press
the Enter button to accept.
The Fault indicator goes steady.
5
Save the configuration and restart
the system
The system restarts.
The system starts in quiescent condition, and the new panel is
operative.